designed to ensure safety at hazardous production
facilities with permanent (technological or purging),
periodic and emergency discharges of combustible gases, by highly
efficient smokeless combustion or dispersion
Design
1. the equivalent diameter of the outlet nozzle of the flare tip can be varied depending on the relief gas flow
2. smokeless/sootless combustion is provided for the entire relief gas flow range without additional air or steam supply
3. the high pressure and low pressure flow can be combined to burn in
one head
Parameter
Value
Working environment
associated petroleum gas, natural gas, various gases from process units
Flare unit capacity, nm3/h
according to customer requirements, permanent/emergency discharge
Operating pressure, MPa (excess pressure)
up to 0,3 and above
Discharge gas temperature, °С
-30 ÷ +300
Average service life before overhaul, h, not less
20 000
Fuel gas consumption for reserve/pilot burners
25
Operating pressure of the fuel gas supplied to the pilot burner, MPa (excess pressure)
0,2 - 0,3
Flame shaft diameter, mm
150 ÷ 1400
Height of the flare unit, mm
10 000 - 120 000
Flame tip diameter, mm
50 - 900
Number of pilot burners, pcs.
1 - 5
Service life, years
up to 30
Power consumption, W, max
200 - 400
Unit type
Smokeless / sootless
control unit (gas treatment unit)
ignition and control system
flare unit
flare stack
flare tip
flash burners
control (local) panel
control cabinet (located locally or in the operator room)
instrumentation within the scope of supply
valving within the scope of supply
spare parts, gaskets, counter flanges
cable products, terminal boxes, electrical and wiring products, cable-support systems within the scope of supply
the design of the flow part of the flare head ensures a constant rate
of discharge (purge) gas, thereby eliminating the possibility of air entering the barrel and
the formation of a combustible, explosive mixture in the flare barrel, thereby replacing the use
of molecular sieves and hydraulic locks as part of the flare installation
the flare head does not require periodic maintenance
all control and measuring and shut-off elements of the ignition and flame control system on duty
the burners are located on the ground at a safe distance behind the torch fence